StandardProducts/Lithiumate/Service/Troubleshooting/ChargingDischarging
Charging or discharging issues
BMS doesn't allow charging
- On the terminal, do Home / Status / System
- What is the CCL value?
-
100 %
-
0 %
- Between 1 and 99 %: the CCL reached 0% in the recent past (at which point discharge was disabled); it will be re-enabled when the CCL reaches 100 %;
- you can wait for it to reach 100 %,
- or you can see why it reached 0% (see above),
- or you can cycle the power off and on
Won't charge, CCL = 100%
- On the terminal, do Home / Status / System
- Is there a fault?
-
u9 StandardProducts/Lithiumate/Service/Troubleshooting/Faultt formattert paget anchort u Yesi ug
-
No
Won't charge, CCL = 100%, no fault
- On the terminal, do Home / Test / Force Outputs / HLIM
- Press Y to activate the HLIM line, N to disactivate it
- Does the charger come on and off?
Won't charge, CCL = 0%
- On the terminal, do Home / Status / Pack
- Temperature:
- What is the minimum temperature? Is it colder than the setting in Home / Set-up / Charge limits / Temperatures / Min?
- What is the maximum temperature? Is it hotter than the setting in Home / Set-up / Charge limits / Temperatures / Max?
- Cell voltage:
- What is the maximum cell voltage? Is it more than the setting in Home / Set-up / Charge limits / Cell voltages / Max?
- Pack voltage:
- What is the maximum pack voltage? Is it more than the setting in Home / Set-up / Charge limits / Pack voltages / Max?
Battery was overcharged
BMS doesn't allow discharging
Battery was over discharged